- Specifications:
- Metering inputs:
- Number: 24
- Voltage ranges: ±2.5, ±5, ±10, ±25, ±50 VDC
- Impedance: 1 MOhms
- Protection: Clamping diode
- Accuracy: 1%
- A/D resolution: 12 bits
- Connector type: Weidmuller pluggable screw terminal
- Status Inputs:
- Number: 24
- Logic levels: High=+2.4 to +12VDC, Low=-12 to +0.8VDC. EIA compatible
- Impedance: >22kOhms
- Protection: Optoisolated
- Ground: Internal or External, individually selectable
- Dry/wet contact: Individually selectable with pull-up resistor
- Connector type: Weidmuller pluggable screw terminal
- Outputs:
- Number: 24
- Type: Form C Relay or Open collector, individually selectable
- Rating: 70VAC @ 0.4A, 30VDC @ 2A. Open collector at 100mA
- Connector type: Weidmuller pluggable screw terminal
- Interface protocol:
- Modbus: RTU or TCP modes
- RTU Mode:
- Connector: USB, RJ-9 for a daisy chain (up to 7 units)
- TCP Mode:
- Connector: RJ-45 (up to 8 units)
- Power Supply: 12 VDC
- Typical current requirements at 12VDC:
- Idle: 150 mA
- Startup: 150 mA
- Max (all relays energized): 480 mA
- Dimensions: 48.3 x 8.7 x 3.6 cm, 19" x 3.44" x 1.42" (including Weidmuller terminals)
- Weight (unit only): 1.3 kg