null

FREE SHIPPING on online orders over $99

Davicom MEXM-1

Davicom

BSW PART:
MEXM-1

Expansion unit with 24 metering inputs, 24 status inputs and 24 relay outputs

Contact BSW for your pricing and shipping!

Want to multiply your Davicom’s input and output points? The MEXM-1 will help you do that! Adding a single MEXM-1 to a DV-Micro yields a total of 32 metering inputs, 32 status inputs and 32 relay outputs for a very low price. These extra I/O’s are directly integrated into the DV-Micro’s control structure, therefore taking full advantage of the Davicom’s powerful control, monitoring and automation functions.

Contact BSW for your pricing and shipping!

Free Shipping

Out of stock

Add to quote
Qualifies for free shipping
  • Specifications:
  • Metering inputs:
  • Number: 24
  • Voltage ranges: ±2.5, ±5, ±10, ±25, ±50 VDC
  • Impedance: 1 MOhms
  • Protection: Clamping diode
  • Accuracy: 1%
  • A/D resolution: 12 bits
  • Connector type: Weidmuller pluggable screw terminal
  • Status Inputs:
  • Number: 24
  • Logic levels: High=+2.4 to +12VDC, Low=-12 to +0.8VDC. EIA compatible
  • Impedance: >22kOhms
  • Protection: Optoisolated
  • Ground: Internal or External, individually selectable
  • Dry/wet contact: Individually selectable with pull-up resistor
  • Connector type: Weidmuller pluggable screw terminal
  • Outputs:
  • Number: 24
  • Type: Form C Relay or Open collector, individually selectable
  • Rating: 70VAC @ 0.4A, 30VDC @ 2A. Open collector at 100mA
  • Connector type: Weidmuller pluggable screw terminal
  • Interface protocol:
  • Modbus: RTU or TCP modes
  • RTU Mode:
  • Connector: USB, RJ-9 for a daisy chain (up to 7 units)
  • TCP Mode:
  • Connector: RJ-45 (up to 8 units)
  • Power Supply: 12 VDC
  • Typical current requirements at 12VDC:
  • Idle: 150 mA
  • Startup: 150 mA
  • Max (all relays energized): 480 mA
  • Dimensions: 48.3 x 8.7 x 3.6 cm, 19" x 3.44" x 1.42" (including Weidmuller terminals)
  • Weight (unit only): 1.3 kg